2 HOUR UL FIRE RATED
FLOOR ASSEMBLY
Fire Resistance Ratings
- ANSI/UL 263
Design No. G575
June 03, 2009
Unrestrained Assembly
Rating — 2 Hr

1.
Flooring System - Building Units* —
Nom 3/4 in. thick. Long dimension of panels to
be perpendicular to joists with end joints staggered
a min of 4 ft and centered over the joists. Panels
secured to steel joists with 1-1/4 in. long self-drilling,
self-countersinking, bugle head steel screws spaced
a max of 12 in. OC in the field with a screw located
1/2 in. from each edge, and 8 in. OC along the
end joints and around the perimeter with a screw
located 1/2 in. from each joint and the side edges
of the panel.
DRAGONBOARD
INC — DragonBoard Flooring
2.
Structural Steel Members* —
The proprietary joists are channel-shaped, min
10 in. deep. Joists are fabricated from min No.
16 MSG galv steel. Joists spaced max 24 in. OC.
At joist rim splices bearing on supports, joists
rims are connected using an overlapping section
of a 12 in. long splice plate (a joist piece),
with four 3/4 in. long No. 10 self-drilling steel
TEK screws to each rim piece.
SUPER
STUD BUILDING PRODUCTS — Type 10SSJ16
3.
Joist Bridging - (Not Shown) —
Installed at the center of the joist span immediately
after joists are erected and before construction
loads are applied. The bridging consists of No.
18 MSG galv steel channels, 2-1/2 in. wide by
22-3/8 in. long with 1/5/8 in. long web extensions
at each end for screw-attachment to the bottom
flange of the steel joists with a 3/4 in. long
No. 10 self-drilling steel TEK screws. Solid bridging
consisting of cut-to-length joist sections placed
between the outermost joists and between the centermost
joists with a max spacing of 8 ft OC.
4. Angle Clips — 2-1/16x4-1/8x13/16x9-7/8
in., No 16 ga clips used to fasten joists to joist
rim track. 4-1/8 in. side of clip placed against
outside web of joists and 2-1/16 in. side placed
against joist rim track. Each side secured with
three #10-3/4 in. TEK screws. 1-1/2x4x8 in., No.
16 ga clips used to fasten joist bridging with
clip located on the web/flange side of the joist.
Clip fastened with two #10-3/4 in. TEK screws
per leg per clip. 1-1/2x1-1/2x8 in, No 16 ga clips
used to fasten joist bridging with clip located
on the web/non-flange side of the joist. Clip
fastened with two #10-3/4 in. TEK screws per leg
per clip.
5.
Batts and Blankets* —
3-1/2 in. thick glass fiber batt insulation draped
over the resilient channels (Item 5) or suspension
system grid (Item 5A). Any glass fiber batt insulation
bearing the UL Classification Marking for Surface
Burning Characteristics having a flame spread
index of 25 or less and a smoke developed index
of 50 or less may be used. See Batts and Blankets
(BKNV) category in the Building Materials Directory
for names of manufacturers.
6.
Resilient Channels — Formed
of No. 25 MSG galv steel, 1/2 in. deep, spaced
max 12 in. OC, perpendicular to joists. Channel
splices located beneath joists and overlapped
4 in.. Channels secured to each joist with one
1/2 in. long Type S-12 low profile steel screw.
Two channels, spaced 6 in. OC, oriented opposite
each gypsum board end joint. Additional channels
shall extend min 6 in. beyond each side edge of
board.
7.
Gypsum Board* — Nom
5/8 in. thick, 48 in. wide gypsum panels. Base
layer installed with long dimension perpendicular
to resilient channels, secured with 1 in. long
Type S bugle-head screws spaced 12 in. OC, with
screws located 6 in. from and on each side of
the gypsum panel, in both the field and the perimeter,
and 1-1/2 in. from side edges of the panels. Face
layer installed with long dimension perpendicular
to resilient channels or cross tees with joints
offset 24 in. from base layer, secured with 1-5/8
in. long Type S bugle-head screws spaced 8 in.,OC,
with screws located 4 in. from and on each side
of the gypsum panel midspan, in both the field
and the perimeter, and 1-1/2 in. from side edges
of the panel. Butt joints of face layer panels
secured to base layer with 1-1/2 in. long Type
G screws spaced 8 in. OC and 1-1/2 in. from side
edges of the panels, with butt joints located
between resilient channels. Butt joints of face
panels staggered a minimum of 12 in. from butt
joints of base layer.
NATIONAL GYPSUM CO — Type FSW-C
8.
Finishing System - (Not Shown) —
Vinyl, dry or premixed joint compound, applied
in two coats to joints and screw-heads. Nom 2
in. wide paper tape embedded in first layer of
compound over all joints. As an alternate, nom
3/32 in. thick veneer plaster may be applied to
the entire surface of gypsum board.
*Bearing the UL Classification
Mark
Last Updated on 2009-06-03
Copyright © 2009 Underwriters
Laboratories Inc.®
The appearance of a company's
name or product in this database does not in itself
assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products
bearing the UL Mark should be considered to be
Listed and covered under UL's Follow-Up Service.
Always look for the Mark on the product.
|